HJA36015

CAPTAIN MEDUSA: Requesting speedy deletion (CSD G11). (TW)



An HJA36015 is a Power Pact H Frame [[Molded case circuit breaker|Molded Case]] [[Circuit breaker|Circuit Breaker]] manufactured by [[Square D]]. The tripping method is Thermal-magnetic and it is used for [[Power distribution|Power Distribution.]]

The HJA Frames are manufactured from 15 to 150 Amps

It has a maximum 600 Volts and a circuit protection rating of 15 amps. The interrupting capacity is 65 kA at 480 V, 25 kA at 600 V, 100 kA at 240 V AC and 20 kA at 250 V DC.

This type of Circuit breaker caries the following certifications CE, CSA, IEC, and is UL listed. It is only used in Square D I-Line type [[Panelboard|Panel-boards]] and has a plug-in mounting connection. It is manufactured with Load Side Lugs Pre-installed.

The physical dimensions are
{| class="wikitable"
!height
|9.73 in
|
|-
!width
|4.48 in
|
|-
!depth
|4.8 in
|}
The H Frame Power Pact type Circuit Breaker is the physical replacement for the Obsolete Square D FC Type Circuit Breaker and is riveted shut for protection against the attempts to alter the internal components for your safety.